E-Clipse Bypass – Programming Notes
Communication Set-up
8. Are you using serial communications?
If no, go to step 9
If yes – select protocol from bypass keypad (Group 98)
STARTUP PARAMS or to 9802 Comm. Protocol Select
Select desired protocol (Embedded Fieldbus)
1= STD MODBUS; 2= N2, 3=FLN; 4 = EXT. FBA; 5 =
BACNET
NOTE: The E-Clipse Bypass communicates to the VFD
using ModBus. No communications settings are
required from the drive keypad.