ACH550-UH User’s Manual 1-305
Technical data
Fuses, 500…600 volt, fuses
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
Generate an emergency stop of the motor.
Separate the drive from dangerous potential.
-124A-4 124 160 175 JJS-175
-125A-4 124
-157A-4 157 200 200 JJS-200
-180A-4 180 250
250 JJS-250
-246A-4 245 315
350 JJS-350
-245A-4 245 Does Not Apply
400 JJS-400
-316A-4 316
400 JJS-400
-368A-4 368
400 JJS-400
-414A-4 414
600 JJS-600
-486A-4 486
600 JJS-600
-526A-4 526
800 JJS-800
-602A-4 602
800 JJS-800
-645A-4 645
800 JJS-800
ACH550-xx-
see below
Input Current
A
Mains Fuses
IEC269 gG (A) UL Class T (A) Bussmann Type
-02A7-6 2.7 10
10 JJS-10
-03A9-6 3.9
-06A1-6 6.1
-09A0-6 9 16
15 JJS-15
-011A-6 11
-017A-6 17 25
25 JJS-25
-022A-6 22
-027A-6 27 35
40 JJS-40
-032A-6 32
-041A-6 41 50
50 JJS-50
-052A-6 52 60
60 JJS-60
-062A-6 62 80
80 JJS-80
-077A-6 77
100 JJS-100
-099A-6 99 125
150 JJS-150
-125A-6 125 160
175 JJS-175
-144A-6 144 200
200 JJS-200
ACH550-UH-
see below
Input Current (A)
Input Fuses
IEC269 gG (A)