E-Clipse Bypass – Communications Set-up
Set-up bypass external communications (if required)
Bypass parameter 5002
Set desired bypass unique network ID (must be different than drive
node number) Default = 256 for most protocols
Address 256 is out of range for most protocols. Therefore, with
address 256, most communication systems will not see the bypass.
For BACnet only, you must set additional parameters
BACnet Bypass Device Object Instance ID – Bypass parameter
5011 / 5017
For BACnet systems, you will need to coordinate with the comms
system integrator and set 5011 for a unique bypass Device Object
Instance ID
Cycle power
Vedere la pagina 27