84 ACS550-01/U1 User’s Manual
Application macros
Macro default values for parameters
Parameter default values are listed in section Complete parameter list on page 87.
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note: There are two sets of values because the defaults are configured for 50 Hz/
IEC compliance (ACS550-01) and 60 Hz/NEMA compliance (ACS550-U1).
ACS550-01
Parameter
ABB
Standard
3-wire Alternate
Motor
Potenti-
ometer
Hand-auto
PID
Control
PFC
Control
Torque
Control
9902
APPLIC MACRO 1=
ABB STANDARD
2=
3-WIRE
3=
ALTERNATE
4=
MOTOR POT
5=
HAND/AUTO
6=
PID CONTROL
7=
PFC CONTROL
8=
TORQUE CTRL
9904 MOTOR CTRL
MODE
3= SCALAR:
FREQ
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
3= SCALAR:
FREQ
2= VECTOR:
TORQUE
1001 EXT1 COMMANDS 2= DI1,2 4= DI1P,2P,3 9= DI1F,2R 2= DI1,2 2= DI1,2 1= DI1 1= DI1 2= DI1,2
1002 EXT2 COMMANDS 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 7= DI6,5 6= DI6 6= DI6 2= DI1,2
1003 DIRECTION 3= REQUEST 3= REQUEST 3= REQUEST 3= REQUEST 3= REQUEST 1= FORWARD 1= FORWARD 3= REQUEST
1102 EXT1/EXT2 SEL 0= EXT10= EXT10= EXT10= EXT13= DI32= DI23= DI33= DI3
1103 REF1 SELECT 1= AI11= AI11= AI112=
DI3U,4D(NC)
1= AI11= AI11= AI11= AI1
1106 REF2 SELECT 2= AI22= AI22= AI22= AI22= AI219= PID1OUT 19 = PID1OUT 2= AI2
1201 CONST SPEED SEL 9= DI3,4 10 = DI4,5 9= DI3,4 5= DI5 0= NOT SEL 9= DI3,4 0= NOT SEL 4= DI4
1304 MINIMUM AI2 0.0% 0.0% 0.0% 0.0% 20.0% 20.0% 20.0% 20.0%
1401 RELAY OUTPUT 1 1= READY 1= READY 1= READY 1= READY 1= READY 1= READY 2= RUN 1= READY
1402 RELAY OUTPUT 2 2= RUN 2= RUN 2= RUN 2= RUN 2= RUN 2= RUN 3= FAULT(-1) 2= RUN
1403 RELAY OUTPUT 3 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 31 = PFC 3= FAULT(-1)
1501 AO1 CONTENT SEL 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
1507 AO2 CONTENT SEL 104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
130 =
PID 1 FBK
104 =
CURRENT
1510 MINIMUM AO2 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 4.0 mA 0.0 mA
1601 RUN ENABLE 0= NOT SEL 0= NOT SEL 6= DI6 6= DI6 4= DI4 5= DI5 2= DI2 6= DI6
2201
ACC/DEC 1/2 SEL 5= DI50= NOT SEL 5= DI50= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 5= DI5
3201 SUPERV 1 PARAM 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
3401 SIGNAL1 PARAM 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
4001 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5 1.0
4002 INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s 60.0 s
4101 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5 1.0
4102
INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s 60.0 s
8123 PFC ENABLE 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 1= ACTIVE 0= NOT SEL