Parameter listing and descriptions 229
ACH550-01 User's Manual
2305 AUTOTUNE RUN 0=OFF, 1=ON
Starts automatic tuning of the speed controller.
0 =
OFF – Disables the Autotune creation process. (Does not disable the
operation of Autotune settings.)
1 =
ON – Activates speed controller autotuning. Automatically reverts to
OFF.
Procedure:
Note: The motor load must be connected.
Run the motor at a constant speed of 20 to 40% of the rated speed.
Change the autotuning parameter 2305 to
ON.
The drive:
• Accelerates the motor.
• Calculates values for proportional gain and integration time.
• Changes parameters 2301 and 2302 to these values.
• Resets 2305 to
OFF.