308 Parameter listing and descriptions
ACH550-01 User's Manual
8119 AUTOCHNG LEVEL 0.0…100.0%
Sets an upper limit, as a percentage of output capacity, for the
autochange logic. When the output from the PID/PFA control block
exceeds this limit, autochange is prevented. For example, use this
parameter to deny autochange when the Pump-Fan system is operating
near maximum capacity.
Autochange overview
The purpose of the autochange operation is to equalise duty time
between multiple motors used in a system. At each autochange
operation:
A different motor takes a turn connected to the ACH550 output – the
speed regulated motor.
The starting order of the other motors rotates.
The Autochange function requires:
external switchgear for changing the drive’s output power
connections.
parameter 8120
INTERLOCKS = value > 0.
Autochange is performed when:
The running time since the previous autochange reaches the time set
by parameter 8118
AUTOCHNG INTERV.
the PFA input is below the level set by parameter 8119
AUTOCHNG
LEVEL.
Code Description Range